Water Treatment Coupon Preparation: Important ASTM Guidance

Summary for water treatment coupon preparation Discussion

Water treatment coupon preparation is debated in this thread, with the question focused on whether corrosion coupons used to judge cooling-water treatment should be passivated to prevent initial "flash corrosion" from skewing results. Pradeep Samajdar asks for a standard or supporting write-up and notes that some leading chemical companies appear to use passivated coupons. Manickam Valliappan points to ASTM G1-03 and ASTM G4 as sources for coupon testing procedures. S. Santhanakrishnan offers the clearest practical caution: in his view, MS, CU, or SS coupons should not be passivated before use in the water treatment system because passivation can produce misleading corrosion figures in MPY. The thread therefore presents differing views, but the main takeaway is to consult the ASTM standards and be careful that any pre-treatment does not distort the measured corrosion rate.

I am a technical sales person in water treatment. I am desirous to know if there is any standard or supporting write up which suggests that metal corrosion coupons which are used to evaluate corrosion protection performance of cooling water treatments should be passivated to avoid the initial “flash corrosion” which may mislead the result. As I understand leading water treatment chemical companies are using passivated coupons for evaluating their treatment program performance.

Pradeep Samajdar
– New Delhi, Delhi, INDIA

2003

A. ASTM G1-03 and ASTM G4 standards will give you more information on the corrosion coupon testing procedures.

Manickam Valliappan
Corrosion Management Services – India
2003

On my understanding, coupons (MS, CU or SS) should not be passivated before application in the water treatment system. Using of passivated coupons may give misleading figures in terms of corrosion units – MPY.

S.Santhanakrishnan
– Pondicherry – INDIA
December 10, 2008